• Transformerless UPS topology
• 3 Level topology
• High input power factor
• High efficiency up to 95%
• Cold start function
• Static and maintenance by-pass switch
• Output short circuit and overload protection
• External REPO switch input
• 512 events memory (512 events 45000 alarms)
• Clock and calendar (battery supported)
• Automatic battery test, remaining battery time indicator
• Temperature compensated charge system (optional)
• 2 RS232 serial ports and 12 dry contact outputs
• 3 DSP controlled modular structure
• Optional SNMP and MODBUS adaptors
• Optional graphical panel
• Optional USB flash memory
• Full digital structure
• Small footprint
• ECO mode operation (optional)
• Fewer electronic components
• Output current limiting
• Advanced diagnostics for the input
• Selectable input / output voltage / frequency / range
• Split by-pass input (second input)
• Output DC leakage protection
• Separate DSP for inverter control
• Separate DSP for the PFC
• 3 level battery protection
• High charge current capacity
• Charge / discharge current indicator
• Advanced remote control
• Manufactured according to EC Directive; EN62040
• 5 years spare parts support
• 2 years warranty
Standige 300-400 KVA Three-phase
The new Standige Three-phase uses the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. With the DS Power range, efficiency, reliability and functionality are enhanced to levels unattainable with the old analogue technology. This technology does not only create significant increase in MTBF, but the capability of DSP to accurately manipulate signals at very high speed permits all the UPS subsystems to be controlled with greatly increased precision.
DS3300H
DS3400H
MODEL
Power (kVA) | 300 |
INPUT
Voltage | 380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load) |
Frequency | 50Hz / 60Hz , ± 5% |
Power factor (at 100% load) | ≥ 0.99 |
THDI (*) | ≤ 3% |
By-pass voltage | 380/400 VAC 3 Phase + N, ± 10% |
Voltage distortion | ≤ 10% |
Protections | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT
Power (kW) | 270 |
Power factor | 0.9 |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency | up to 95% |
Crest factor | 3:1 |
Overload capacity | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
VoltageTHD | ≤ 3% (at 100% linear load) |
BATTERY
Type | VRLA AGM / GEL / NiCd |
Number of batteries | 2x30 (±30) : 60 pieces |
Charge voltage | 2x405 VDC |
End of discharge voltage | 2x300 VDC |
Battery cabinet | External |
Battery ambient temperature | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic testing | Standard every 72 hours (adjustable) |
GENERAL
Standards | EN62040-1, EN62040-2, EN62040-3 |
User interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
Indicators | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset kit | Standard (programmable) |
Software | Standard T-Mon UPS Management Software (3 clients + 1 server management) |
Alarm logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature ranges | 0ºC - 40ºC |
Protection degree | IP20 |
Relative humidity | 95% max. (non-condensing) |
Altitude | < 1000m above sea level |
Acoustic noise | < 68 Dba |
Net weight (kg) | 635 |
Dimensions (mm) HxWxD | 1900x1250x775 |
OPTIONS
Different input / output voltage | Please ask |
Transformer | Galvanic isolation transformer at the input & output (internal) |
Software | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parallel operation | up to 8 units |
MODEL
Power (kVA) | 400 |
INPUT
Voltage | 380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load) |
Frequency | 50Hz / 60Hz , ± 5% |
Power factor (at 100% load) | ≥ 0.99 |
THDI (*) | ≤ 3% |
By-pass voltage | 380/400 VAC 3 Phase + N, ± 10% |
Voltage distortion | ≤ 10% |
Protections | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT
Power (kW) | 360 |
Power factor | 0.9 |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency | up to 95% |
Crest factor | 3:1 |
Overload capacity | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
Voltage THD | ≤ 3% (at 100% linear load) |
BATTERY
Type | VRLA AGM / GEL / NiCd |
Number of batteries | 2x30 (±30) : 60 pieces |
Charge voltage | 2x405 VDC |
End of discharge voltage | 2x300 VDC |
Battery cabinet | External |
Battery ambient temperature | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic testing | Standard every 72 hours (adjustable) |
GENERAL
Standards | EN62040-1, EN62040-2, EN62040-3 |
User interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
Indicators | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Input | EPO input, Interactive battery panel input, Genset input |
Genset kit | Standard (programmable) |
Software | Standard T-Mon UPS Management Software (3 clients + 1 server management) |
Alarm logging | Standard: with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature ranges | 0ºC - 40ºC |
Protection degree | IP20 |
Relative humidity | 95% max. (non-condensing) |
Altitude | < 1000m above sea level |
Acoustic noise | < 68 Dba |
Net weight (kg) | 680 |
Dimensions (mm) HxWxD | 1900x1250x775 |
OPTIONS
Different input / output voltage | Please ask |
Transformer | Galvanic isolation transformer at the input & output (internal) |
Software | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parallel operation | Up to 8 hours |
Reviews