Aktiv 1–3 kVA Single-Phase

Aktiv / Aktiv+ series is the new generation of small power UPS by Enertech, Both input and output are single phase and output power factor is 0.8.The efficiency of this UPS is very high, it can achieve considerable power saving and reduce total cost of ownership in result.

SKU: Aktiv 1–3 kVA Category:

Description

Aktiv / Aktiv +

Aktiv / Aktiv+ series is the new generation of small power UPS by Enertech, Both input and output are single phase and output power factor is 0.8.The efficiency of this UPS is very high, it can achieve considerable power saving and reduce total cost of ownership in result.

Absolute protection

The UPS systems of the Aktiv / Aktiv+ series guarantee highest protection and highest quality of care for all kinds of applications, especially mission-critical applications such as security systems and electromedical devices, and Industrial and telecommunication processes as well.
Aktiv / Aktiv+ is an uninterruptible double converter online system of class VFI SS 111 according to IEC (EN-62040-3). The power range of Aktiv / Aktiv+ is from 1kVA to 10kVA.

Easy source

Aktiv / Aktiv+ increases efficiency and simplifies supply of the UPS by power generators.
In addition, the losses in the system and in the windings, and the corrected power factor and eliminated harmonics, which are also generated by loads and the UPS itself, has been reduced in this series.

Power continuity

Enertech has been developing for many years, several solutions to meet different requirements and solve problems in the field critical applications there.
Enertech offers adaptable High level solutions of availability, which is different plant structures and the different security levels to adjust.
Enertech produces resilient UPS systems that are capable to solve a variety of faults in components and systems compensate without any interrupt to the continuous supply of the consumer.
This is accomplished by installing redundant elements and through careful planning to remedy the general points of failure, to carry out planned maintenance and monitoring the operating and environmental parameters. The employees of the technical services are ready to give you advice and provide solutions for your projects.

Flexibility

Aktiv / Aktiv+ series is suitable for every type of application, from IT to medical units, and industrial conditions. Thanks to the large selection of options, complex systems can be implemented that ensure maximum availability of particularly critical consumers.

Battery protection system (BPS):

maximum protection of the batteries is normally achieved by the rectifier; in the event of a power failure, the UPS uses this energy source to supply its own consumers. An effective battery management system is therefore essential to ensure the desired protection in an emergency.

easy installation

Very little space is required to install Aktiv / Aktiv+. In addition, installing internal serials does not require any specialization and electrical acknowledgment, just plug in, and use the UPS backward outlets.

Special solutions

The UPS can be adapted to the specific requirements of the application. Contact our technicians, for specifications and special solutions that are not listed in the catalog.

Advanced communication

  • Compatible with SNPM for remote monitoring.
  • Advanced communication, multi-platform for all operating systems and network environments. Monitoring and shutdown through Power-Shield software is included, with SNMP protocol, for operating systems Windows 2008, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris Linux, and other
  • The UPS is equipped with a cable for direct connection to a PC (plug and play)
  • Double serial interface RS232
  • Also there is a USB connection port for using with monitoring systems which do not have RS232 ports.

 OPTIONS

  • Emergency Power Off (EPO)
  • SNMP card for monitoring system
  • Relay Card
  • Online double conversion
  • Wide input voltage range (110-300Vac)
  • Input power factor 0.99 (With PFC)
  • Output power factor 0.9
  • Maximum charging current 12A (Long run unit)
  • Charging current can be set by LCD
  • 50Hz/60Hz frequency converter mode
  • Emergency power off function (EPO) – Optional
  • Eco mode operation for energy saving (ECO)
  • Generator compatible
  • USB / RS232 multiple communications
  • SNMP / Relay Card (Optional)
  • Smart battery charging design for optimized battery performance
  • Selectable output voltage: 200, 208, 220, 230, 240Vac
  • Low priority load disconnection function
  • Smart battery charging design for optimizing battery performance
  • 1A or 2A charging current can be selected2A charging current is for 2 groups of inside batteries
1KVA S 1KVA L 2KVA S 2KVA L 3KVA L
GENEREAL
Capacity (VA/Watts) 1000VA/900W
INPUT
Nominal Voltage 208/ 220/230/240Vac (L+N+PE)
Voltage Range 110~300Vac
Frequency Range 50Hz:45~55Hz,60Hz: 55-65Hz Auto Sensing
Power Factor 0.99
OUTPUT
Output Voltage 208/220/230/240Vac:230Vac (Default)
Power Factor 0.9 (1 is optional)
Voltage Regulation ±1%
Frequency Synchronized Range
Crest Factor 3:1
(THDv) ≤2% with linear load / ≤4% with non-linear load
Waveform Pure Sinewave
Transfer Time Utility to Battery: 0ms; Utility to Bypass: 4ms (Typical)
Efficiency 88%
BATTERY
Battery Type Sealed Lead Acid VRLA Batteries
DC Voltage 24VDC – 36VDC (optional)
Battery Number 2 × 9AH (3 Optional)
Maximum Charging Current (A) * 1A
PROTECTION
Overload Capacity 105%-110% for 10min / 110%-130% for 1min / 130%-150% for 30 second
Other Protections Short Circuit / Over Heat / Battery Low / Over Voltage
Alarms Line Failure / Battery Low / Over Load / System Fault
BY-PASS >150% :UPS transfer to to bypass when utility is normal
PHYSICAL ENVIRONMENT
Dimension (W×H×D) S 144×209×293
Dimension (W×H×D) L 144×209×293
Weight (kg) 9.8
Temperature 0℃~40℃
Humidity Range 0~95% (Non-condensing)
Altitude < 1500m
Noise Level <50dB @ 1Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2 IEC61000-4-2 / IEC61000-4-3 / IEC61000-4-4 / IEC61000-4-5 / IEC61000-4-6 / 1EC610000-4-8
GENEREAL
Capacity (VA/Watts) 1000VA/900W
INPUT
Nominal Voltage 208/ 220/230/240Vac (L+N+PE)
Voltage Range 110~300Vac
Frequency Range 50Hz:45~55Hz,60Hz: 55-65Hz Auto Sensing
Power Factor 0.99
OUTPUT
Output Voltage 208/220/230/240Vac:230Vac (Default)
Power Factor 0.9 (1 is optional)
Voltage Regulation ±1%
Frequency Synchronized Range
Crest Factor 3:1
(THDv) ≤2% with linear load / ≤4% with non-linear load
Waveform Pure Sinewave
Transfer Time Utility to Battery: 0ms; Utility to Bypass: 4ms (Typical)
Efficiency 88%
BATTERY
Battery Type Sealed Lead Acid VRLA Batteries
DC Voltage 24VDC – 36VDC (optional)
Battery Number 2 × 9AH (3 Optional)
Maximum Charging Current (A) * 12A
PROTECTION
Overload Capacity 105%-110% for 10min / 110%-130% for 1min / 130%-150% for 30 second
Other Protections Short Circuit / Over Heat / Battery Low / Over Voltage
Alarms Line Failure / Battery Low / Over Load / System Fault
BY-PASS >150% :UPS transfer to to bypass when utility is normal
PHYSICAL ENVIRONMENT
Dimension (W×H×D) S 144×209×293
Dimension (W×H×D) L 144×209×293
Weight (kg) 4
Temperature 0℃~40℃
Humidity Range 0~95% (Non-condensing)
Altitude < 1500m
Noise Level <50dB @ 1Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2 IEC61000-4-2 / IEC61000-4-3 / IEC61000-4-4 / IEC61000-4-5 / IEC61000-4-6 / 1EC610000-4-8
GENEREAL
Capacity (VA/Watts) 2000VA/1800W
INPUT
Nominal Voltage 208/ 220/230/240Vac (L+N+PE)
Voltage Range 110~300Vac
Frequency Range 50Hz:45~55Hz,60Hz: 55-65Hz Auto Sensing
Power Factor 0.99
OUTPUT
Output Voltage 208/220/230/240Vac:230Vac (Default)
Power Factor 0.9 (1 is optional)
Voltage Regulation ±1%
Frequency Synchronized Range
Crest Factor 3:1
(THDv) ≤2% with linear load / ≤4% with non-linear load
Waveform Pure Sinewave
Transfer Time Utility to Battery: 0ms; Utility to Bypass: 4ms (Typical)
Efficiency 92%
BATTERY
Battery Type Sealed Lead Acid VRLA Batteries
DC Voltage 48VDC – 72VDC (optional)
Battery Number 4 × 9AH (6 Optional)
Maximum Charging Current (A) * 1A
PROTECTION
Overload Capacity 105%-110% for 10min / 110%-130% for 1min / 130%-150% for 30 second
Other Protections Short Circuit / Over Heat / Battery Low / Over Voltage
Alarms Line Failure / Battery Low / Over Load / System Fault
BY-PASS >150% :UPS transfer to to bypass when utility is normal
PHYSICAL ENVIRONMENT
Dimension (W×H×D) S 144×209×309
Dimension (W×H×D) L 144×209×309
Weight (kg) 17
Temperature 0℃~40℃
Humidity Range 0~95% (Non-condensing)
Altitude < 1500m
Noise Level <50dB @ 1Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2 IEC61000-4-2 / IEC61000-4-3 / IEC61000-4-4 / IEC61000-4-5 / IEC61000-4-6 / 1EC610000-4-8
GENEREAL
Capacity (VA/Watts) 2000VA/1800W
INPUT
Nominal Voltage 208/ 220/230/240Vac (L+N+PE)
Voltage Range 110~300Vac
Frequency Range 50Hz:45~55Hz,60Hz: 55-65Hz Auto Sensing
Power Factor 0.99
OUTPUT
Output Voltage 208/220/230/240Vac:230Vac (Default)
Power Factor 0.9 (1 is optional)
Voltage Regulation ±1%
Frequency Synchronized Range
Crest Factor 3:1
(THDv) ≤2% with linear load / ≤4% with non-linear load
Waveform Pure Sinewave
Transfer Time Utility to Battery: 0ms; Utility to Bypass: 4ms (Typical)
Efficiency 92%
BATTERY
Battery Type Sealed Lead Acid VRLA Batteries
DC Voltage 48VDC – 72VDC (optional)
Battery Number 4 × 9AH (6 Optional)
Maximum Charging Current (A) * 12A
PROTECTION
Overload Capacity 105%-110% for 10min / 110%-130% for 1min / 130%-150% for 30 second
Other Protections Short Circuit / Over Heat / Battery Low / Over Voltage
Alarms Line Failure / Battery Low / Over Load / System Fault
BY-PASS >150% :UPS transfer to to bypass when utility is normal
PHYSICAL ENVIRONMENT
Dimension (W×H×D) S 144×209×309
Dimension (W×H×D) L 144×209×309
Weight (kg) 6.7
Temperature 0℃~40℃
Humidity Range 0~95% (Non-condensing)
Altitude < 1500m
Noise Level <50dB @ 1Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2 IEC61000-4-2 / IEC61000-4-3 / IEC61000-4-4 / IEC61000-4-5 / IEC61000-4-6 / 1EC610000-4-8
GENEREAL
Capacity (VA/Watts) 3000VA/2700W
INPUT
Nominal Voltage 208/ 220/230/240Vac (L+N+PE)
Voltage Range 110~300Vac
Frequency Range 50Hz:45~55Hz,60Hz: 55-65Hz Auto Sensing
Power Factor 0.99
OUTPUT
Output Voltage 208/220/230/240Vac:230Vac (Default)
Power Factor 0.9 (1 is optional)
Voltage Regulation ±1%
Frequency Synchronized Range
Crest Factor 3:1
(THDv) ≤2% with linear load / ≤4% with non-linear load
Waveform Pure Sinewave
Transfer Time Utility to Battery: 0ms; Utility to Bypass: 4ms (Typical)
Efficiency 92%
BATTERY
Battery Type Sealed Lead Acid VRLA Batteries
DC Voltage 72VDC – 96VDC (optional)
Battery Number 6 × 9AH (8 Optional)
Maximum Charging Current (A) * 12A
PROTECTION
Overload Capacity 105%-110% for 10min / 110%-130% for 1min / 130%-150% for 30 second
Other Protections Short Circuit / Over Heat / Battery Low / Over Voltage
Alarms Line Failure / Battery Low / Over Load / System Fault
BY-PASS >150% :UPS transfer to to bypass when utility is normal
PHYSICAL ENVIRONMENT
Dimension (W×H×D) S 191×337×460
Dimension (W×H×D) L 144×209×309
Weight (kg) 7.3
Temperature 0℃~40℃
Humidity Range 0~95% (Non-condensing)
Altitude < 1500m
Noise Level <50dB @ 1Meter
STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2 IEC61000-4-2 / IEC61000-4-3 / IEC61000-4-4 / IEC61000-4-5 / IEC61000-4-6 / 1EC610000-4-8